상세 보기
Comparison of Metallic Particle Behaviour According to AC and DC Voltage
- Ryu, Chanyeol;
- Lee, Bangwook
SCOPUS
0초록
Gas Insulated Switchgear (GIS) concentrates the electric field locally when metallic particles levitate inside that cause breakdown when contacting high-voltage conductors. Therefore, research to prevent metallic particle levitation is continuously required. Previous studies indicate that the behaviour of metallic particles depending on the AC and DC voltage and particle shape. Additionally, most research presents particle behaviour analysis through simulations, without providing detailed methods. In this paper, a levitation experiment was conducted on spherical and wire metallic particles on a parallel flat plate electrode under AC and DC voltage in an SF6 gas environment at atmospheric pressure. The recorded video was analysed using the Tracker 6.1.6 program to analyse the entire behaviour of the particles, according to shape, AC and DC and polarity. © The Institution of Engineering & Technology 2024.