Evaluation and parametric optimization of the thermal performance and cost effectiveness of active-indirect solar hot water plants

Citations

SCOPUS

31

초록

In the study, an investigation and comparison of the thermal performance and cost effectiveness of an active-indirect solar hot water plant (SHWP) at Incheon (Korea), Jeddah (Saudi Arabia) and Changi (Singapore) international airports are carried out. Plant performances are analyzed for various collector areas and storage tank volumes at the ASHRAE standard flow rate and are reported in terms of the annual solar fraction, solar thermal rating, as well as the capital payback period and annualized life cycle savings. The main objective of this study is to optimize a SHWP that supplies water at 65°C to a flight kitchen for the economic benefits for an average daily energy demand. For the energy demand of 100 m3/day, the minimum payback periods of SHWPs at Incheon, Jeddah and Changi airports are 8.94 years with Ac= 1140 m2and Vt= 32 m3, 5.91 years with Ac= 750 m2and Vt= 24 m3and 8.39 years with Ac= 1050 m2and Vt= 28 m3, respectively. © 2015, Novel Carbon Resource Sciences. All rights reserved.

키워드

Economic evaluation; Parametric optimization; Simulation; Solar hot water system
제목
Evaluation and parametric optimization of the thermal performance and cost effectiveness of active-indirect solar hot water plants
저자
Kim, Young deuk; Thu, Kyaw; Ng, Kim choon
DOI
10.5109/1544080
발행일
2015-09
유형
Article
저널명
Evergreen
권
2
호
2
페이지
50 ~ 60