온수분배기용 유량제어밸브의 개발

Development of Flow Control Valves for Hot Water Distribution Manifolds

초록

The developed control valves, installed on the hot water distribution manifolds for the floor heating system, consist of the balancing valves and the shut-off valves. The balancing valve was designed to improve the flow control performance and to reduce the noise emitted from the valve by modification of the general V port. The port of the shut-off valve was designed with two ceramic plates, working by rotating upper plate, to improve the duration and to reduce the noise. For the evaluation of the new valves, the flow rate was measured and noise level test was carried out. The test results showed that the error of the flow rate accuracy test for the flow balance of each manifold circuit was less than ±3% and the noise level was less than 35dB(A).

키워드

Hot water distribution manifolds; Central heating system; Individual heating system; Flow rate; Control valve; 온수분배기; 중앙난방; 개별난방; 유량; 제어밸브
제목
온수분배기용 유량제어밸브의 개발
제목 (타언어)
Development of Flow Control Valves for Hot Water Distribution Manifolds
저자
권우철; 윤준용; 유선학
DOI
10.5293/KFMA.2010.13.4.011
발행일
2010-08
저널명
한국유체기계학회 논문집
권
13
호
4
페이지
11 ~ 17