지중송전케이블 종단접속함 종류에 따른 외기 및 운전온도에 의한 열특성 분석

Thermal Characteristics Analysis by Ambient and Operating Temperature according to the Kinds of Terminations in Underground Power Cable Systems
Citations

SCOPUS

0

초록

This paper describes the thermal characteristics of underground power cable system terminations according to the change of ambient temperature as well as operating temperature. Recently, the failure has been gradually increasing in outdoor termination during winter season because the power demand was increased by electricity heating system. The power demand and outdoor temperature is difference between day time and night time. The temperature difference has an influence on conductor extension and shrinkage due to conductor force as well as thermal mechanical characteristics. These phenomena have daily repeated during heating and cooling period of conductors. In these cases, the insulation of outdoor terminations might be degraded by the reduced interface pressure surrounding stress relief cone. Therefore, in this paper, the thermal characteristics are variously analysed by simulation considering power demand and ambient temperature condition during winter season at epoxy type termination as well as slip-on type termination

키워드

ComsolFailureOutdoor terminationUnderground power cables
제목
지중송전케이블 종단접속함 종류에 따른 외기 및 운전온도에 의한 열특성 분석
제목 (타언어)
Thermal Characteristics Analysis by Ambient and Operating Temperature according to the Kinds of Terminations in Underground Power Cable Systems
저자
정채균강지원이방욱
DOI
10.5370/KIEE.2015.64.8.1154
발행일
2015-08
저널명
전기학회논문지
64
08
페이지
1154 ~ 1160