Numerical and experimental investigation on backward fitting effect on valve flow coefficient

Citations

WEB OF SCIENCE

7
Citations

SCOPUS

5

초록

This study investigates the effect of the attached fitting on the valve flow coefficient. Four types of fittings were mounted on the downstream of a valve. It is concluded that the valve flow coefficient must be corrected by a piping geometric factor around 0.81, regardless of the type of the fitting attached.

키워드

control valve; valve flow coefficient; piping geometry factor; PERFORMANCE
제목
Numerical and experimental investigation on backward fitting effect on valve flow coefficient
저자
Kang, S-K; Yoon, J-Y; Kang, S-H; Lee, B-H
DOI
10.1243/0954408JPME87
발행일
2006-11
유형
Article
저널명
Proceedings of the Institution of Mechanical Engineers, Part E: Journal of Process Mechanical Engineering
권
220
호
4
페이지
217 ~ 220