Islanding Detection Method for Grid-Forming Inverter by Reactive Power Injection

Citations

SCOPUS

1

초록

The operation of grid-connected inverters in islanding presents critical issues for grid operation, utility workers' safety, and stakeholders, due to the control of voltage magnitude and frequency, reconnection caused by phase mismatch, among others. In such cases, grid-following inverters can detect islanding due to their current source operational characteristics, whether they are supplying 100% power or not. However, grid-forming inverters, during islanding with droop control, supply power at a frequency lower than the grid frequency under load, and cannot detect islanding when not supplying power due to their voltage source operation mode. To overcome this limitation of grid-forming inverters, this paper proposes a method to detect islanding by injecting reactive power into the power command of the droop controller. The method is validated through simulations in a 380V/60Hz system using PSCAD/EMTDC. © The Institution of Engineering & Technology 2024.

키워드

GRID-FORMING INVERTER; ISLANDING DETECTION; REACTIVE POWER INJECTION
제목
Islanding Detection Method for Grid-Forming Inverter by Reactive Power Injection
저자
Kim, Minseung; Lee, Eun S.
DOI
10.1049/icp.2024.2407
발행일
2024-07
유형
Conference paper
저널명
IET Conference Proceedings
권
2024
호
6
페이지
962 ~ 967